


TROUBLE
SHOOTING GUIDE Due to the robust direct
design of the Hawk Pressure Reducing Valve, more
often than not it is factors other than the valve itself which cause malfunctions.
Here we shall illustrate problems that may arise In scenarios which may involve
the valve, but are not a consequence of the valve and its design. The Inlet pressure
could be below the desired set valve, or could have dropped since the last
time it was set. Pressure Guage could
be faulty. Drop in outlet pressure
when there is downstream flow This is quite normal, and not a fault. It is
due to the head-toss in the pipeline on the inlet side, and also the inherent
head-loss across the valve. For more details please refer to the section about
head-loss calculation above. However, if the head-loss Is too large, it means
that the valve size selected is too smalt or the pipe diameter is not large
enough Setting was done when
water was flowing through the valve. To correct this, please reset the valve
properly, i.e. open the adjustment screw completely (anti-clockwise), open
a tap downstream to bleed the system, close all taps, then reset the valve
to the desired pressure. Pressure Guage could
be faulty. Back Pressure in the
system. This could tie caused due to a back pressure build up in a heater
or any other such appliance where water is heated and expands (100 litres
of water at 15°C expands to 102 liters at 70°C). In normal circumstances,
this is prevented by a Non Return Valve on the inlet side of the heater, but
when this valve is faulty or worn or could be working erratically due to bad
spring quality/seat mechanism. Damage to the internals
of the internals of the valve due to a "pressure-slam" or "water-hammer".Seating
& seat cage mechanism in the valve could be bent/broken. Bypass allows the inlet
pressure to pass into the outlet side,due to faulty isolation valves.This
makes what is wrongly considered to be a safety feature into the problem itself.
WE DO NOT RECOMMEND USING A BYPASS SYSTEM WITH OUR VALVES,AS IT IS ALMOST
NEVER POSSIBLE FOR THE VALVE TO SHUT DOWN FLOW COMPLETELY,UNLIKE SOME MAKES
OF VALVES WHICH SHUT OFF FLOW IN CIRCUMSTANCES NOT IDEAL FOR THEIR FUNCTIONING.
Only one of the inlet
pipelines (either hot/cold water) is fitted with a Pressure Reducing Valve.There
could be leakage into the other pipeline through a mixer.
Pressure Reducing Valve Stops Flow :
Caused by the valve being fitted wrongly, back to front. Check the
arrow on the valve body and fit correctly.
Outlet Pressure is Below Setting :
Directionally wrong adjustment.
Outlet Pressure Is Above Setting :
The outlet pressure setting lies outside the limits of the valve, as
explained in the "Adjustment Range" charts of the valve.
Inlet And Outlet Pressure Are Equal
Incorrect pressure setting,caused due to excessive tightening of the
adjusting screw. To rectify,slacken the screw and reset.